Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T06FR00385
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/14/2006 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 904.11.2- The actuation of the fire extinguishing system shall automatically shut down the fuel or electrical power supply to the cooking equipment and all electrical receptacles located within the perimeter of the hood. The resets shall be manual. *I will need documentation that the gas and electricity is shut off upon activation of the fire extinguishing system. This must be performed by qualified personnel. |
|
03/14/2006 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 901.6- Fire extinguishing systems hsall be maintained in operative condition at all times. *Coverage for griddle and stove + rice cooker shall have coverage. *Nozzles shall have grease caps installed. |
|
03/14/2006 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 906.7- Fire extinguishers shall be anchored securely within 30 feet of cooking operations, near an exit. |