Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/16/2006

Applicant:

OTTIMO 22ND GROUP LLC (THE)

Description:

Inspection

Outstanding Inspections

Case Number: T06FR00202
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
10/25/2005 VIOL - ADMINISTRATION JLANGEJA Violation
10/25/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 102.6- No building or structure shall be used or occupied until the building official has issued a Certificate of Occupancy
10/25/2005 VIOL - EMERGENCY PLAN/PREPARE JLANGEJA Violation TFC 407.2- Material Safety Data Sheets for all hazardous materials shall be readily available on the premises. 1. toner 2.developer
10/25/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space of not less than 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment. 1. server room 2. mail room, all panels
10/25/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.4.2- Relocatable power taps shall be directly connected to a permanently installed receptacle. 1. server room x 2 2. printer on south wall 3. west wall in front office 4. Clarissa Vasquez's office 5. mail room
10/25/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be used as a substitute for permanent wiring. 1. server room 2. Peggy Payton's office 3. Conference room 4. printer outside lunch room 5. Gloria Lucas's office 6. Monica Ahumada's office
10/25/2005 VIOL - FIRE RESIST.RATED CONST JLANGEJA Violation TFC 703.1- Fire resistive-rated construction shall be maintained. Ceiling tile shall be installed properly. (server room)
10/25/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishers shall be serviced annually. (several throughout)
10/25/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.7- Fire extinguishers shall be installed on their hangers or brackets. (server room)
10/25/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1006.3- Emergency lighting shall function properly in the event of a power failure. 1. server room 2. conference room 3. break room