Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T06FR00202

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
10/25/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.4.2- Relocatable power taps shall be directly connected to a permanently installed receptacle.
1. server room x 2
2. printer on south wall
3. west wall in front office
4. Clarissa Vasquez's office
5. mail room
10/25/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5- Extension cords shall not be used as a substitute for permanent wiring.
1. server room
2. Peggy Payton's office
3. Conference room
4. printer outside lunch room
5. Gloria Lucas's office
6. Monica Ahumada's office
10/25/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- A working space of not less than 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment.
1. server room
2. mail room, all panels