Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T06FR00202
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.4.2- Relocatable power taps shall be directly connected to a permanently installed receptacle. 1. server room x 2 2. printer on south wall 3. west wall in front office 4. Clarissa Vasquez's office 5. mail room |
|
10/25/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall not be used as a substitute for permanent wiring. 1. server room 2. Peggy Payton's office 3. Conference room 4. printer outside lunch room 5. Gloria Lucas's office 6. Monica Ahumada's office |
|
10/25/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3- A working space of not less than 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment. 1. server room 2. mail room, all panels |