Case: T05FR01779
Case Details
Entered Date:
11/14/2005
Applicant:
CP PLAZA LLC
Description:
blocked exits. aisle width. overstocked store.
Outstanding Inspections
Case Number: T05FR01779
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
VIOL - MEANS OF EGRESS | None | Not Inspected | ||
11/15/2005 | INSP - FULL | RSUMMER | Correction Required | jdavis2 assigned. |
11/22/2005 | VIOL - PRECAUTION AGAINST FIRE | JDAVIS | Correction Required | Section 1003.6 Obstructions shall not be placed in the required width of an exit: currently both rear exits are blocked by stock -Fire exits shall be cleared immediately Section 1016.1/ 1003.3 Aisle width shall be maintained at all times Section 1013.4.1 B and M occupancies: Minimum clear aisle width shall be not less than 36 inches |
11/22/2005 | VIOL - PRECAUTION AGAINST FIRE | JDAVIS | Correction Required | Section 314.2. Fixtures and displays of goods for sale to te public shall be arranged so as to maintain free and immediate and unobstructed access to exits as required by Chapter 10 Section 315.2.2 Means of egress: combustible materials shall not be stored in exit or exit enclosures |
Completed Inspections
Case Status: FIELD
Case Number: T05FR01779
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/22/2005 | COMPL - INITIAL INSPECTION | JDAVIS | Approved |