Case: T05FR01779

Parcel: 140122210


Addresses:

2032 E IRVINGTON RD


Inspection Status: Correction Required

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Case Number - T05FR01779

Inspection Description - VIOL - PRECAUTION AGAINST FIRE

Inspection Status - Correction Required

Date Description Inspector Results Comments
11/22/2005 VIOL - PRECAUTION AGAINST FIRE Correction Required Section 314.2.
Fixtures and displays of goods for sale to te public shall be arranged so as to maintain free and immediate and unobstructed access to exits as required by Chapter 10

Section 315.2.2
Means of egress:
combustible materials shall not be stored in exit or exit enclosures
11/22/2005 VIOL - PRECAUTION AGAINST FIRE Correction Required Section 1003.6
Obstructions shall not be placed in the required width of an exit:
currently both rear exits are blocked by stock
-Fire exits shall be cleared immediately

Section 1016.1/ 1003.3
Aisle width shall be maintained at all times

Section 1013.4.1
B and M occupancies: Minimum clear aisle width shall be not less than 36 inches