Case: T05FR01776
Case Details
Entered Date:
11/14/2005
Applicant:
OSTROY IRVING & SHIRLEY UND 25% INT
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR01776
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 18
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/14/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2 Storage of combustible materials in basement shall be orderly. Storage shall not be maintained under stairway. |
11/14/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage in the basement shall be maintained 2 feet below the level of the ceiling. |
11/14/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage located in the kitchen shall be maintained 2 feet below the level of the ceiling. |
11/14/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Power cords located at the toasters and the above power strip shall be repaired where damaged. |
11/14/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.4 The multiplug adapter located in the kitchen at the west wall is prohibited and shall not be used. |
11/14/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.4.1 The powerstrip located in the kitchen by the toasters shall be replaced with a type equipped with overcurrent protection. |
11/14/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 The extinsion cord located in the basement and extending up the stairway shall not be used in place of permanent wiring. |
11/14/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The wall located on the west side of the stairwell shall be repaired. Wallboard shall be replaced. |
11/14/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 The portable fire extinguisher located in the kitchen shall be inspected annually. |
11/14/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.3 The commercial cooking system hood shall be cleaned at regular intervals to prevent the accumulation of grease. |
11/14/2005 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.4 The commercial cooking system extinguishing system shall be serviced every 6 months. |
11/14/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1003.6/1027.2 The means of egress for the area in front of the cooking appliances shall not be diminished along the path of egress travel. Space shall be provided to exit the cooking area. |
11/14/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8.3 A sign shall be posted on the egress side of the main north exit stating This door to remain unlocked when building is occupied. |
11/14/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 The exit sign located at the southeast exit shall be repaired so that it remains lit at all times. |
11/14/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.5 The emergency illumination light located at the lobby near the main north exit shall be repaired so that it will light in the event of power supply failure. |
11/14/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 Stairway shall remain free from obstructions. No storage shall remain on stairway. |
11/14/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 The exit hallway at the southeast exit shall be maintained free from obstructions. |
11/14/2005 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.3 The compressed gas cylinder located at the east bar area shall be secured to prevent it from falling. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01776
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/01/2005 | INSP - FULL | TKNAPP | Approved |