Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/14/2005

Applicant:

OSTROY IRVING & SHIRLEY UND 25% INT

Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR01776
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 18
End Date Description Inspector Results Comments
11/14/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2 Storage of combustible materials in basement shall be orderly. Storage shall not be maintained under stairway.
11/14/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage in the basement shall be maintained 2 feet below the level of the ceiling.
11/14/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage located in the kitchen shall be maintained 2 feet below the level of the ceiling.
11/14/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 Power cords located at the toasters and the above power strip shall be repaired where damaged.
11/14/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.4 The multiplug adapter located in the kitchen at the west wall is prohibited and shall not be used.
11/14/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.4.1 The powerstrip located in the kitchen by the toasters shall be replaced with a type equipped with overcurrent protection.
11/14/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 The extinsion cord located in the basement and extending up the stairway shall not be used in place of permanent wiring.
11/14/2005 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 The wall located on the west side of the stairwell shall be repaired. Wallboard shall be replaced.
11/14/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 The portable fire extinguisher located in the kitchen shall be inspected annually.
11/14/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.6.3 The commercial cooking system hood shall be cleaned at regular intervals to prevent the accumulation of grease.
11/14/2005 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.6.4 The commercial cooking system extinguishing system shall be serviced every 6 months.
11/14/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1003.6/1027.2 The means of egress for the area in front of the cooking appliances shall not be diminished along the path of egress travel. Space shall be provided to exit the cooking area.
11/14/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.3 A sign shall be posted on the egress side of the main north exit stating This door to remain unlocked when building is occupied.
11/14/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 The exit sign located at the southeast exit shall be repaired so that it remains lit at all times.
11/14/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.5 The emergency illumination light located at the lobby near the main north exit shall be repaired so that it will light in the event of power supply failure.
11/14/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 Stairway shall remain free from obstructions. No storage shall remain on stairway.
11/14/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 The exit hallway at the southeast exit shall be maintained free from obstructions.
11/14/2005 VIOL - COMPRESSED GASES TKNAPP Correction Required 3003.3 The compressed gas cylinder located at the east bar area shall be secured to prevent it from falling.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01776
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/01/2005 INSP - FULL TKNAPP Approved