Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T05FR01776

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
11/14/2005 VIOL - MEANS OF EGRESS Correction Required 1008.1.8.3 A sign shall be posted on the egress side of the main north exit stating This door to remain unlocked when building is occupied.
11/14/2005 VIOL - MEANS OF EGRESS Correction Required 1026.5 The emergency illumination light located at the lobby near the main north exit shall be repaired so that it will light in the event of power supply failure.
11/14/2005 VIOL - MEANS OF EGRESS Correction Required 1026.3 The exit sign located at the southeast exit shall be repaired so that it remains lit at all times.
11/14/2005 VIOL - MEANS OF EGRESS Correction Required 1027.2 The exit hallway at the southeast exit shall be maintained free from obstructions.
11/14/2005 VIOL - MEANS OF EGRESS Correction Required 1027.2 Stairway shall remain free from obstructions. No storage shall remain on stairway.
11/14/2005 VIOL - MEANS OF EGRESS Correction Required 1003.6/1027.2 The means of egress for the area in front of the cooking appliances shall not be diminished along the path of egress travel. Space shall be provided to exit the cooking area.