Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T05FR01635
Case Details
Entered Date:
10/13/2005
Applicant:
EL MOLINTO INC
Description:
fullinspection
Outstanding Inspections
Case Number: T05FR01635
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2005 | INSP - FULL | FCONTRER | Correction Required | 2003 TFC-605.5 Extension cords shall not be substitute for permanant wiring. Remove and replace with power surge protector.Front entrance of business and behind the ice-cream machine. TFC-1008.1.2 The means of egress, including the exit discharge shall be illuminated at all times.Fix and repair the exit signs and back up lights. TFC-605.3 Junction box in back cooking area and the one under the hood shall have the cover plates to prevent electrical shock. TFC-3003.3.3 Compress gas cylinders shall be secured to a fix object to prevent failing, |