Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T05FR01635
Inspection Description - INSP - FULL
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2005 | INSP - FULL | Correction Required | 2003 TFC-605.5 Extension cords shall not be substitute for permanant wiring. Remove and replace with power surge protector.Front entrance of business and behind the ice-cream machine. TFC-1008.1.2 The means of egress, including the exit discharge shall be illuminated at all times.Fix and repair the exit signs and back up lights. TFC-605.3 Junction box in back cooking area and the one under the hood shall have the cover plates to prevent electrical shock. TFC-3003.3.3 Compress gas cylinders shall be secured to a fix object to prevent failing, |