Type:

INSPECTION

Entered Date:

10/07/2005

Applicant:

SANTOS DANIEL JR & CAROL J TR

Description:

fire inspection

Outstanding Inspections

Case Number: T05FR01577
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
10/07/2005 VIOL - MEANS OF EGRESS JDAVIS Correction Required 1011.2 1. North Exit shall be illuminated 2. Front exit door shall have an illuminated exit sign installed 1008.1,8.4/ 1008.1.8.3 #2.2 Exits shall be openable from the inside without use of a key or speacial knowledge: Currently the rear exit has a gate installed with a double-ley locking device. 605.3/ 605.1 THe electrical panel in the hpone room shall have a blank installed where the breakwer is missing. 703.1 Fire resistive construction shall be maintained. Replace the ceiling tile in the bathroom. 3003.3 Compressed gas cylinders shall be secure against accidental dislodgement. 906.7 Fire extinguishers shall be properly mounted. Currently the extinguisher in the kitchen is sitting on the floor. Notes: Hood sytem and been serviced. Filters are also clean. CofO is properly posted (OL=89)

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01577
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/07/2005 INSP - FULL JDAVIS Approved