Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

10/05/2005

Applicant:

TUCSON SUMMITT LLC

Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR01559
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
10/05/2005 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2 Storage of combustible materials in the building shall be orderly.
10/05/2005 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required 505.1 Address numbers shall be posted on the building. Numbers shall be in accordance with Pima County address display requirements.
10/05/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 The open junction boxes located in the north room on the north wall and on the north east corner of the press shall have approved covers.
10/05/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8 The 2 westside exits shall not be equipped with a lock requiring a key from the egress side.
10/05/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.4 The manually operated flush bolt lock on the northwest exit is not permitted and shall be removed.
10/05/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required A cover shall be provided for the electrical breaker panel on the north wall of the south room.
10/05/2005 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1504.6 Spray painting operations shall not be conducted within the building or spray booth. The spray booth shall be brought into compliance with the TFC before any spraying operations are conducted.
10/05/2005 VIOL - WELDING & OTHER HOT WRK TKNAPP Correction Required 2604.1.1 Hot work areas shall not contain combustibles.
10/05/2005 VIOL - WELDING & OTHER HOT WRK TKNAPP Correction Required 2604.1.3 Floors in the hot work areas shall be kept clean.
10/05/2005 VIOL - WELDING & OTHER HOT WRK TKNAPP Correction Required 2604.2.6 One 2A:20BC portable fire extinguisher shall be provided in each room used for hot work.
10/05/2005 VIOL - HAZARDOUS MATERIALS,GEN TKNAPP Correction Required 2703.5.1 The fiftyfive gallon drums located inside and outside the building that are empty shall be labled empty.
10/05/2005 VIOL - COMPRESSED GASES TKNAPP Correction Required 3003.3.3 All compressed gas cylinders shall be secured to prevent them from falling.