Case: T05FR01559
Case Details
Entered Date:
10/05/2005
Applicant:
TUCSON SUMMITT LLC
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR01559
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
10/05/2005 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2 Storage of combustible materials in the building shall be orderly. |
10/05/2005 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 505.1 Address numbers shall be posted on the building. Numbers shall be in accordance with Pima County address display requirements. |
10/05/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction boxes located in the north room on the north wall and on the north east corner of the press shall have approved covers. |
10/05/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 The 2 westside exits shall not be equipped with a lock requiring a key from the egress side. |
10/05/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8.4 The manually operated flush bolt lock on the northwest exit is not permitted and shall be removed. |
10/05/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | A cover shall be provided for the electrical breaker panel on the north wall of the south room. |
10/05/2005 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1504.6 Spray painting operations shall not be conducted within the building or spray booth. The spray booth shall be brought into compliance with the TFC before any spraying operations are conducted. |
10/05/2005 | VIOL - WELDING & OTHER HOT WRK | TKNAPP | Correction Required | 2604.1.1 Hot work areas shall not contain combustibles. |
10/05/2005 | VIOL - WELDING & OTHER HOT WRK | TKNAPP | Correction Required | 2604.1.3 Floors in the hot work areas shall be kept clean. |
10/05/2005 | VIOL - WELDING & OTHER HOT WRK | TKNAPP | Correction Required | 2604.2.6 One 2A:20BC portable fire extinguisher shall be provided in each room used for hot work. |
10/05/2005 | VIOL - HAZARDOUS MATERIALS,GEN | TKNAPP | Correction Required | 2703.5.1 The fiftyfive gallon drums located inside and outside the building that are empty shall be labled empty. |
10/05/2005 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.3.3 All compressed gas cylinders shall be secured to prevent them from falling. |