Case: T05FR01559

Parcel: 107061240


Addresses:

1201 W MIRACLE MILE


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T05FR01559

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
10/05/2005 VIOL - MEANS OF EGRESS Correction Required 1008.1.8 The 2 westside exits shall not be equipped with a lock requiring a key from the egress side.
10/05/2005 VIOL - MEANS OF EGRESS Correction Required 1008.1.8.4 The manually operated flush bolt lock on the northwest exit is not permitted and shall be removed.
10/05/2005 VIOL - MEANS OF EGRESS Correction Required A cover shall be provided for the electrical breaker panel on the north wall of the south room.