Case Number: T05FR01500
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
09/21/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 102.3- Change of use or occupancy. The provisions of the International Existing Building Code shall apply to all buildings undergoing a change of use or change of occupancy. |
09/21/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 110.1- No building or structure shall be used or occupied and no change in the existing occupancy classification of a building or structure until the building official has issued a Certificate of Occupancy. *The Child Activity Center should be classified as a Child Daycare in the Eoccupancy classification, possibly an I-4 depending on occupant load. |
09/21/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.1- Storage shall be maintained a minimum of 18" below sprinkler head deflectors. |
09/21/2005 | VIOL - EMERGENCY PLAN/PREPARE | JLANGEJA | Violation | TFC 407.2- Material Safety Data Sheets for all Hazardous materials shall be readily available on the premises. |
09/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605 4. Multiplug adapters, such as cube adapters, unfused plug strips or any other devise not complying with the ICC Electrical Code shall be prohibited. (room #3) |
09/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of not less than 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30", the working space shall not be less than the width of the equipment. 1. janitor's closet- panels and transformer 2. IT room- panels and transformer |
09/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.4.2- Relocatable power taps shall be directly connected to a permanently installed receptacle. 1. room #9 (1) 2. room #11 (8) 3. room #14 (8) 4. room #15 (2) 5. room #17 (1) 6. library (1) |
09/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. 1. room #1 2. room #11 x (5) 3. room #14 4. room #15 |
09/21/2005 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Violation | TFC 703.1- Fire resistive-rated construction shall be maintained. Such elements shall be repaired, restored or replaced when damaged, altered, breached or penetrated. (ceiling tile in janitor's closet) |
09/21/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers shall be serviced annually. (room #14) |
09/21/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.7- Fire extinguishers shall be installed on their hangers or brackets. (room #14) |
10/18/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1027.6- Where panic hardware or fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door. Remove one set from North (rear) exit. |