Case Number: T05FR01500
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
09/21/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 102.3- Change of use or occupancy. The provisions of the International Existing Building Code shall apply to all buildings undergoing a change of use or change of occupancy.
09/21/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 110.1- No building or structure shall be used or occupied and no change in the existing occupancy classification of a building or structure until the building official has issued a Certificate of Occupancy. *The Child Activity Center should be classified as a Child Daycare in the Eoccupancy classification, possibly an I-4 depending on occupant load.
09/21/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2.1- Storage shall be maintained a minimum of 18" below sprinkler head deflectors.
09/21/2005 VIOL - EMERGENCY PLAN/PREPARE JLANGEJA Violation TFC 407.2- Material Safety Data Sheets for all Hazardous materials shall be readily available on the premises.
09/21/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605 4. Multiplug adapters, such as cube adapters, unfused plug strips or any other devise not complying with the ICC Electrical Code shall be prohibited. (room #3)
09/21/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space of not less than 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30", the working space shall not be less than the width of the equipment. 1. janitor's closet- panels and transformer 2. IT room- panels and transformer
09/21/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.4.2- Relocatable power taps shall be directly connected to a permanently installed receptacle. 1. room #9 (1) 2. room #11 (8) 3. room #14 (8) 4. room #15 (2) 5. room #17 (1) 6. library (1)
09/21/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring. 1. room #1 2. room #11 x (5) 3. room #14 4. room #15
09/21/2005 VIOL - FIRE RESIST.RATED CONST JLANGEJA Violation TFC 703.1- Fire resistive-rated construction shall be maintained. Such elements shall be repaired, restored or replaced when damaged, altered, breached or penetrated. (ceiling tile in janitor's closet)
09/21/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishers shall be serviced annually. (room #14)
09/21/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.7- Fire extinguishers shall be installed on their hangers or brackets. (room #14)
10/18/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1027.6- Where panic hardware or fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door. Remove one set from North (rear) exit.