Case: T05FR01500

Parcel: 12809006B


Addresses:

5441 E 22ND ST #125


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T05FR01500

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
09/21/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring.
1. room #1
2. room #11 x (5)
3. room #14
4. room #15
09/21/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605 4. Multiplug adapters, such as cube adapters, unfused plug strips or any other devise not complying with the ICC Electrical Code shall be prohibited. (room #3)
09/21/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- A working space of not less than 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30", the working space shall not be less than the width of the equipment.
1. janitor's closet- panels and transformer
2. IT room- panels and transformer
09/21/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.4.2- Relocatable power taps shall be directly connected to a permanently installed receptacle.
1. room #9 (1)
2. room #11 (8)
3. room #14 (8)
4. room #15 (2)
5. room #17 (1)
6. library (1)