Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. 1. room #1 2. room #11 x (5) 3. room #14 4. room #15 |
|
| 09/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605 4. Multiplug adapters, such as cube adapters, unfused plug strips or any other devise not complying with the ICC Electrical Code shall be prohibited. (room #3) | |
| 09/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3- A working space of not less than 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30", the working space shall not be less than the width of the equipment. 1. janitor's closet- panels and transformer 2. IT room- panels and transformer |
|
| 09/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.4.2- Relocatable power taps shall be directly connected to a permanently installed receptacle. 1. room #9 (1) 2. room #11 (8) 3. room #14 (8) 4. room #15 (2) 5. room #17 (1) 6. library (1) |