Outstanding Inspections

Case Number: T05FR01451
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
09/19/2005 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Correction Required TFC605.3 Electrical panel next to rear exit in stockroom is obstructed.A working spsce of not less than 30" in width,36"in depth and 78" in height shall be provided in front of electrical service equipment.No storage of any materials shall be located within the designated working space.
09/19/2005 VIOL - MEANS OF EGRESS DRAMIREZ Correction Required TFC1026.3 Exit sign to rear exit of stockroom is not illuminated.Must be illuminated at all times and visable under emergency situations.