Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 09/19/2005 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
TFC605.3 Electrical panel next to rear exit in stockroom is obstructed.A working spsce of not less than 30" in width,36"in depth and 78" in height shall be provided in front of electrical service equipment.No storage of any materials shall be located within the designated working space. |