Case Number: T05FR01360
Case Status: REFERRED
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
08/30/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 102.6- No building or structure shall be used or occupied until the building official has issued a Certificate of Occupancy.
08/30/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space of not less than 30" width, 36" depth and 78" height shall be provided in front of electrical service equipment. 1. N wal of break room 2. E wall of break room
08/30/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.4- Multiplug adapters, such as cube adapters, unfused plug strips or any device not complying with the ICC Electrical Code shall be prohibited. 1. N wall of break room 2. E wall of office #1 3. E wall of office #3
08/30/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring. 1. N wall of break room 2. E wall of office #1 3. E wall of office #3
08/30/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1003.6- The path of egress travel shall not be interrupted. *Blinds over door shall be removed.
08/30/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1008.1.8- Doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. *Replace double-keyed cylinder with a thumb latch*