Case: T05FR01360
Case Details
Entered Date:
08/31/2005
Applicant:
OTTIMO 22ND GROUP LLC (THE)
Description:
Inspection
Outstanding Inspections
Case Number: T05FR01360
Case Status: REFERRED
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
08/30/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 102.6- No building or structure shall be used or occupied until the building official has issued a Certificate of Occupancy. |
08/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of not less than 30" width, 36" depth and 78" height shall be provided in front of electrical service equipment. 1. N wal of break room 2. E wall of break room |
08/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.4- Multiplug adapters, such as cube adapters, unfused plug strips or any device not complying with the ICC Electrical Code shall be prohibited. 1. N wall of break room 2. E wall of office #1 3. E wall of office #3 |
08/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. 1. N wall of break room 2. E wall of office #1 3. E wall of office #3 |
08/30/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1003.6- The path of egress travel shall not be interrupted. *Blinds over door shall be removed. |
08/30/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1008.1.8- Doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. *Replace double-keyed cylinder with a thumb latch* |