Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T05FR01360
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3- A working space of not less than 30" width, 36" depth and 78" height shall be provided in front of electrical service equipment. 1. N wal of break room 2. E wall of break room |
|
08/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. 1. N wall of break room 2. E wall of office #1 3. E wall of office #3 |
|
08/30/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.4- Multiplug adapters, such as cube adapters, unfused plug strips or any device not complying with the ICC Electrical Code shall be prohibited. 1. N wall of break room 2. E wall of office #1 3. E wall of office #3 |