Case: T05FR01360

Parcel: 12809006B


Addresses:

5441 E 22ND ST #107

Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
08/30/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- A working space of not less than 30" width, 36" depth and 78" height shall be provided in front of electrical service equipment.
1. N wal of break room
2. E wall of break room
08/30/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring.
1. N wall of break room
2. E wall of office #1
3. E wall of office #3
08/30/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.4- Multiplug adapters, such as cube adapters, unfused plug strips or any device not complying with the ICC Electrical Code shall be prohibited.
1. N wall of break room
2. E wall of office #1
3. E wall of office #3