Outstanding Inspections

Case Number: T05FR00932
Case Status: PRECITE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
06/21/2005 VIOL - LUMBER YARD & WOOD FAC. EGRIFFIN Violation 1). Currently there is woodworking in this facility. A portable fire extinguisher is required to b obtained and mounted. TFC 1904.2 1904.2 Portable fire extinguishers and hose. Portable fire extinguishers or standpipes and hose supplied from an approved water system shall be provided within 50 feet (15 240 mm) of travel distance to any machine producing shavings or sawdust. Extinguishers shall be provided in accordance with Section 906 for extra-high hazards. Size 4A is required. TFC C906.3.(1)
07/18/2005 INSP - REINSPECTION EGRIFFIN Violation 1). Due to woodworking, portable fire extinguisher is required. Fire extinguisher shall be at least size 4A. TFC 1904.2. This letter is to inform you that abatement of these Tucson Fire Code violations must be completed by 8-1-05. A re-inspection shall be conducted at that time to ensure compliance