Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - LUMBER YARD & WOOD FAC.
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/21/2005 | VIOL - LUMBER YARD & WOOD FAC. | Violation | 1). Currently there is woodworking in this facility. A portable fire extinguisher is required to b obtained and mounted. TFC 1904.2 1904.2 Portable fire extinguishers and hose. Portable fire extinguishers or standpipes and hose supplied from an approved water system shall be provided within 50 feet (15 240 mm) of travel distance to any machine producing shavings or sawdust. Extinguishers shall be provided in accordance with Section 906 for extra-high hazards. Size 4A is required. TFC C906.3.(1) |