Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T05FR00932

Parcel: 12908088C

Inspection Status: Violation

Inspection History: VIOL - LUMBER YARD & WOOD FAC.

Case Number - T05FR00932

Inspection Description - VIOL - LUMBER YARD & WOOD FAC.

Inspection Status - Violation

Date Description Inspector Results Comments
06/21/2005 VIOL - LUMBER YARD & WOOD FAC. Violation 1). Currently there is woodworking in this facility. A portable fire extinguisher is required to b obtained and mounted. TFC 1904.2

1904.2 Portable fire extinguishers and hose. Portable fire extinguishers or standpipes and hose supplied from an approved water system shall be provided within 50 feet (15 240 mm) of travel distance to any machine producing shavings or sawdust. Extinguishers shall be provided in accordance with Section 906 for extra-high hazards.

Size 4A is required. TFC C906.3.(1)