Case: T05FR00925
Case Details
Entered Date:
06/21/2005
Applicant:
BECK RUDY C
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00925
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
06/21/2005 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1504.1 Spray finishing operations are not being conducted within a spray room, spray booth, or limited spraying space. |
06/21/2005 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1504.1.4.1 The aggregate surface to be sprayed shall not be over 9 square feet in a limited spraying space |
06/21/2005 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1504.1.4.2 Spray finishing operations conducted in a limited spraying space shall not be of a continuous nature. |
06/21/2005 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1504.1.4.3 Ventilation system in spray area does not meet the requirements for handling flammable vapors. |
06/21/2005 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1504.1.4.4 Electrical wiring within 10 feet of the floor and 20 feet horizontally shall be Class 1, Division 2. |
06/21/2005 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1504.6.4 Area shall have a 4A-40B extinguisher within 30 feet. |