Case: T05FR00486
Case Details
Entered Date:
04/15/2005
Applicant:
SMITHS FOOD & DRUG CENTERS INC
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00486
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 The electrical panel cover located in the receiving area hallway shall be securely fastened to the panel. |
04/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 The power cord for the pepsi machine outside on the west side of the building shall be repaired. |
04/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 The electrical panels located in the maintenance room near the main enterance shall have clear 36 inch deep working space in front of them. |
04/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 The electrical panels located in the storage room upstairs shall have a clear 36 inch deep working space in front of them. |
04/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 The yellow and orange extension cords located in the bakery shall not be used as a substitute for permanent wiring or extended through the ceiling. |
04/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction box, in the loft area near the refrigeration equipment outside the double doors, shall have an approved cover. |
04/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction box, in the produce work area, shall have an approved cover. |
04/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction box, in the recieving area near rhe south exit, shall have an approved cover. |
04/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction box, outside at the southwest corner, shall have an approved cover. |
04/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction box, outside near the phones, shall have an approved cover. |
04/15/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 The open junction box, outside on the west side near the enterance, shall have an approved cover. |
04/15/2005 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 The missing ceiling tile in the maintenance room near the main enterance shall be replaced. |
04/15/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.6 Where panic hardware is installed, it shall be the only locking device on the door. The padlock on the frozen delivery door shall be removed. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00486
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/29/2005 | INSP - FULL | TKNAPP | Approved |