Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 04/15/2005 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
605.6 The open junction box, outside at the southwest corner, shall have an approved cover. |
| 04/15/2005 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
605.6 The open junction box, outside near the phones, shall have an approved cover. |
| 04/15/2005 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
605.6 The open junction box, outside on the west side near the enterance, shall have an approved cover. |
| 04/15/2005 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
605.6 The open junction box, in the produce work area, shall have an approved cover. |
| 04/15/2005 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
605.6 The open junction box, in the recieving area near rhe south exit, shall have an approved cover. |
| 04/15/2005 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
605.6 The open junction box, in the loft area near the refrigeration equipment outside the double doors, shall have an approved cover. |
| 04/15/2005 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
605.1 The power cord for the pepsi machine outside on the west side of the building shall be repaired. |
| 04/15/2005 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
605.3 The electrical panels located in the maintenance room near the main enterance shall have clear 36 inch deep working space in front of them. |
| 04/15/2005 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
605.3 The electrical panels located in the storage room upstairs shall have a clear 36 inch deep working space in front of them. |
| 04/15/2005 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
605.5 The yellow and orange extension cords located in the bakery shall not be used as a substitute for permanent wiring or extended through the ceiling. |
| 04/15/2005 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
605.1 The electrical panel cover located in the receiving area hallway shall be securely fastened to the panel. |