Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/06/2005

Applicant:

SKLIAS DIMITRIOS & MARIA JT/RS

Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR00464
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 16
End Date Description Inspector Results Comments
04/06/2005 VIOL - ADMINISTRATION TKNAPP Correction Required 111.1 The two small single burner ranges shall not be used unless they are located under and protected by the hood extinguishing system.
04/06/2005 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required 505.1 Address numbers shall be posted in accordance with Pima County requirements.
04/06/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605 The light fixtures in the stockroom shall be repaired so wiring is not exposed.
04/06/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 Electrical panel in kitchen area shall have blanks inserted in areas where breakers are missing.
04/06/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 Junction box at coffee machine area celing shall be secured.
04/06/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 Working space shall be maintained in front of electrical panel.
04/06/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 Extinsion cords shall not be a substitute for permanent wiring. Extension cords shall be removed.
04/06/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 Open junction boxes shall have approved covers.
04/06/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1004.3 The occupant load in the main dining area shall be posted.
04/06/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1006.1 Emergency lighting shall be installed in patio area
04/06/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1006.1 The dining area shall have emergency lighting installed.
04/06/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.3 A sign shall be posted at the front exit gate stating This door to remain unlocked when building is occupied.
04/06/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.9 Panic hardware shall be installed on south patio exit.
04/06/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1011.1 Illuminated exit sign shall be installed at north patio exit
04/06/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1011.1 Illuminated exit sign shall be installed at south patio exit
04/06/2005 VIOL - COMPRESSED GASES TKNAPP Correction Required 3003.3 Compressed gas cylinders shall be secured.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00464
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/27/2005 INSP - FULL TKNAPP Approved