Case: T05FR00464
Case Details
Entered Date:
04/06/2005
Applicant:
SKLIAS DIMITRIOS & MARIA JT/RS
Description:
Full Inspection
Outstanding Inspections
Case Number: T05FR00464
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 16
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2005 | VIOL - ADMINISTRATION | TKNAPP | Correction Required | 111.1 The two small single burner ranges shall not be used unless they are located under and protected by the hood extinguishing system. |
| 04/06/2005 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 505.1 Address numbers shall be posted in accordance with Pima County requirements. |
| 04/06/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605 The light fixtures in the stockroom shall be repaired so wiring is not exposed. |
| 04/06/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Electrical panel in kitchen area shall have blanks inserted in areas where breakers are missing. |
| 04/06/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Junction box at coffee machine area celing shall be secured. |
| 04/06/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 Working space shall be maintained in front of electrical panel. |
| 04/06/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extinsion cords shall not be a substitute for permanent wiring. Extension cords shall be removed. |
| 04/06/2005 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Open junction boxes shall have approved covers. |
| 04/06/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1004.3 The occupant load in the main dining area shall be posted. |
| 04/06/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1006.1 Emergency lighting shall be installed in patio area |
| 04/06/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1006.1 The dining area shall have emergency lighting installed. |
| 04/06/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8.3 A sign shall be posted at the front exit gate stating This door to remain unlocked when building is occupied. |
| 04/06/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.9 Panic hardware shall be installed on south patio exit. |
| 04/06/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1011.1 Illuminated exit sign shall be installed at north patio exit |
| 04/06/2005 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1011.1 Illuminated exit sign shall be installed at south patio exit |
| 04/06/2005 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.3 Compressed gas cylinders shall be secured. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR00464
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/27/2005 | INSP - FULL | TKNAPP | Approved |