Case: T05FR00464

Parcel: 11305067A


Addresses:

1730 E PRINCE RD


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T05FR00464

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
04/06/2005 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.5 Extinsion cords shall not be a substitute for permanent wiring. Extension cords shall be removed.
04/06/2005 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.6 Open junction boxes shall have approved covers.
04/06/2005 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.1 Junction box at coffee machine area celing shall be secured.
04/06/2005 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.1 Electrical panel in kitchen area shall have blanks inserted in areas where breakers are missing.
04/06/2005 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3 Working space shall be maintained in front of electrical panel.
04/06/2005 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605 The light fixtures in the stockroom shall be repaired so wiring is not exposed.