Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/09/2005

Applicant:

CIRILLO MARK D

Description:

inspection

Outstanding Inspections

Case Number: T05FR00231
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
02/09/2005 INSP - FULL EGRIFFIN Violation 1). Currently fire access road have "narrowed" from the required 20 width. There are 2 roads, and both are necessary. Also an additional road shall be maintained in rear of lot, as discussed. Tucson Fire Codes state: 503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm), except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches (4115 mm). Maintain (widen) all fire access roads to 20 feet in width. Establish new road to rear of property.
02/09/2005 INSP - FULL EGRIFFIN Violation 2). Currently no ABC multi-purpose, type extinguisher exist on property, and both water extinguishes are in need of recharge. TFC 2604.2.6 states; 2604.2.6 Fire extinguisher. A minimum of one portable fire extinguisher complying with Section 906 and with a minimum 2-A:20-B:C rating shall be readily accessible within 30 feet (9144 mm) of the location where hot work is performed. 2-A 20-BC extinguishers shall be within 30 feet of all hot work operations. Both water extinguishers shall be recharged and maintained. TFC 901.6
02/09/2005 INSP - FULL EGRIFFIN Violation 3). Currently no ABC type extinguisher exists in shop area, where flammable liquids are being used, and auto repair, and work is also being done. 2-A 20-BC extinguishers shall be mounted and accessible in shop area. TFC 2205.2
02/09/2005 INSP - FULL EGRIFFIN Violation 4). Currently pile of tires is adjacent to property line. TFC Section 25. Tires shall be 10 feet from fence, And or property line

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00231
Case Description: INSPECTION
Total Completed Inspections - 3
End Date Description Inspector Results Comments
05/31/2005 COMPLIANCE EGRIFFIN Approved ok
05/31/2005 VIOL - FIRE SERVICE FEATURES EGRIFFIN Approved ok
05/31/2005 INSP - REINSPECTION EGRIFFIN Approved ok