Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - REINSPECTION
Case Number - T05FR00231
Inspection Description - INSP - REINSPECTION
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/31/2005 | INSP - REINSPECTION | Approved | ok | |
03/14/2005 | INSP - REINSPECTION | Violation | 1). Currently fire access road have "narrowed" from the required 20 width. There are 2 roads, and both are necessary. Also an additional road shall be maintained in rear of lot, as discussed. Tucson Fire Codes state: 503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm), except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches (4115 mm). Maintain (widen) all fire access roads to 20 feet in width. Establish new road to rear of property. 2). Currently no ABC multi-purpose, type extinguisher exist on property, and both water extinguishes are in need of recharge. TFC 2604.2.6 states; 2604.2.6 Fire extinguisher. A minimum of one portable fire extinguisher complying with Section 906 and with a minimum 2-A:20-B:C rating shall be readily accessible within 30 feet (9144 mm) of the location where hot work is performed. 2-A 20-BC extinguishers shall be within 30 feet of all hot work operations. Both water extinguishers shall be recharged and maintained. TFC 901.6 |