Case: T04VL00807
Case Details
Entered Date:
12/06/2004
Applicant:
GONZVAR PETER & AUXILADORA JT/RS
Description:
COMPLAINT: EMER CALL OUT - RTCD - ELECTRICAL SHORT/OVERLOAD OF CIRCUIT.
Outstanding Inspections
Case Number: T04VL00807
Case Status: COMPLIAN
Case Description: RES: FIRE
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2004 | INITIAL CODE VIOLATION | LHANLY | Violation | ELECTRICAL SHORT/CIRCUIT OVERLOAD IN S.E. BEDROOM, MINOR SCORCHING AND SMOKE BRANCH CIRCUIT REQUIRES REPAIR - PERMIT REQUIRED . OLD HOUSE HAS A 110V DROP TO TWO 30 AMP FUSES. SOMEONE BY-PASSED FUSES ALLOWING CURRENT OVERLOAD - BRANCH CIRCUIT TO BEDROOM (CEILING LIGHT TO RECEPTACLE LEG) REQUIRES REPAIR AND HOME MUST BE PROPERLY FUSED./ BYPASSED FUSES AT 110V 30A DROP ALLOWED MC CABLE IN CEILING TO ARC AND START SMALL ROOF FIRE. PERMITS REQUIRED FOR ELECTRIC REPAIR. |
Completed Inspections
Case Status: COMPLIAN
Case Number: T04VL00807
Case Description: RES: FIRE
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/27/2004 | FOLLOW UP CODE VIOLATION | RHENDRIC | Approved | 12/20/04 - PERMIT T04CM05287 WAS ISSUED ON 12/06/04 FOR ELEC REPAIRS. PERMIT WAS FINALED ON 12/08/04 BY D SANTA CRUZ OK TO CLOSE |