Case: T04VL00705
Case Details
Entered Date:
11/01/2004
Applicant:
BLOCK HOUSE APT LLC
Description:
COMPLAINT: EMER CALL OUT C FIRE - UNITS 86, 85, 70 - PERMIT REQUIRED FOR REPAIRS.
Outstanding Inspections
Case Number: T04VL00705
Case Status: COMPLIAN
Case Description: COM: FIRE
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2004 | INITIAL CODE VIOLATION | LHANLY | Violation | UNIT 86 EXTENSIVE SHEETROCK DAMAGE, HEAT DAMAGED WIRES AND OUTLETS, EXHAUST FAN AND DUCT IN BATHROOM REQUIRES REPAIR. - UNIT 85 MINOR DAMAGE IN BATH AND MECH ROOM. UNIT 70 - WATER DAMAGE. / MET WITH MAINT MAN AND WALKED SITE TRYING TO FIND DISCONNECTS TO 2 AFFECTED APTS. WHEN NO DISCONNECT COULD BE FOUND DECISION WAS MADE BY DSD TO SHUT DOWN POWER TO WHOLE BLDG. I MADE DECISION BECAUSE OF SEVERE ARCING IN SUB PANEL OF UNIT 70. NIETHER MTCE PERSON NOR MGR KNEW WHERE ANY PANELS WERE THAT CONTROLLED INDIVIDUAL UNITS. MGT MUST FIND AND LABEL ALL DISCONNECTS. MAIN DISCONNECTS TO BE LOCATED AND LABELED WITHIN 5 DAYS. SUB PANELS IN APTS TO BE DONE WITHIN 30 DAYS. |
Completed Inspections
Case Status: COMPLIAN
Case Number: T04VL00705
Case Description: COM: FIRE
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/17/2004 | FOLLOW UP CODE VIOLATION | MCAPISTR | Approved | 12/15/04 - JOHN OF TA BUILDERS REPORTS RICK BRIGHT ARCHITECTS WILL SUBMIT INFO AND PLANS ON 12/15/04 FOR PERMITS |