Inspection History Details
Inspection Status: Violation
Inspection History: INITIAL CODE VIOLATION
Case Number - T04VL00705
Inspection Description - INITIAL CODE VIOLATION
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2004 | INITIAL CODE VIOLATION | Violation | UNIT 86 EXTENSIVE SHEETROCK DAMAGE, HEAT DAMAGED WIRES AND OUTLETS, EXHAUST FAN AND DUCT IN BATHROOM REQUIRES REPAIR. - UNIT 85 MINOR DAMAGE IN BATH AND MECH ROOM. UNIT 70 - WATER DAMAGE. / MET WITH MAINT MAN AND WALKED SITE TRYING TO FIND DISCONNECTS TO 2 AFFECTED APTS. WHEN NO DISCONNECT COULD BE FOUND DECISION WAS MADE BY DSD TO SHUT DOWN POWER TO WHOLE BLDG. I MADE DECISION BECAUSE OF SEVERE ARCING IN SUB PANEL OF UNIT 70. NIETHER MTCE PERSON NOR MGR KNEW WHERE ANY PANELS WERE THAT CONTROLLED INDIVIDUAL UNITS. MGT MUST FIND AND LABEL ALL DISCONNECTS. MAIN DISCONNECTS TO BE LOCATED AND LABELED WITHIN 5 DAYS. SUB PANELS IN APTS TO BE DONE WITHIN 30 DAYS. |