Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/07/2004

Applicant:

SCHONFELD CHARLES W 1996 INTER VIVOS TR 1/2 &

Description:

Full Inspection

Outstanding Inspections

Case Number: T04FR00741
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
12/07/2004 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Ceiling clearance - Storage in the beverage storage area and in the northside stockroom shall be maintained 18 inches below the level of the sprinkler heads.
12/07/2004 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.3 Equipment rooms - Combustible materials shall not be stored in electrical equipment rooms.
12/07/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.3 A readily visible sign shall be posted near the front main exit stating "This door to remain unlocked when building is occupied".
12/07/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 Exit sign illumination - The exit sign at the front main southside exit shall be lit at all times.
12/07/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 Reliability - The exit corridor on the northeast corner of the store shall be completely free from obstructions or storage.

Completed Inspections

Case Status: COMPLETE
Case Number: T04FR00741
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/23/2004 INSP - FULL TKNAPP Approved