Inspection Status: Correction Required
Inspection History: VIOL - PRECAUTION AGAINST FIRE
Case Number - T04FR00741
Inspection Description - VIOL - PRECAUTION AGAINST FIRE
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/07/2004 | VIOL - PRECAUTION AGAINST FIRE | Correction Required | 315.2.1 Ceiling clearance - Storage in the beverage storage area and in the northside stockroom shall be maintained 18 inches below the level of the sprinkler heads. | |
12/07/2004 | VIOL - PRECAUTION AGAINST FIRE | Correction Required | 315.2.3 Equipment rooms - Combustible materials shall not be stored in electrical equipment rooms. |