End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
10/05/2004 VIOL - EMERGENCY PLAN/PREPARE TKNAPP Correction Required 407.2 Material Safety Data Sheets - Material Safety Data Sheets shall be readily available on the premises.
10/05/2004 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1503.2.1.1 Spray spaces and vapor areas - Electrical wiring and equipment in spray spaces and vapor areas shall be of an explosion proof type.
10/05/2004 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1503.2.6 Smoking Prohibited - No smoking signs shall be posted near spray booth area and near paint storage area.
10/05/2004 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1503.2.7 Welding warning signs - Welding warning signs shall be posted near spray booth.
10/05/2004 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1504.1.2.5 Clear space - A clear space of 3 feet shall be maintained around spray booths.
10/05/2004 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1504.6 Fire Protection - Spray booths shall be protected by an approved automatic fire extinguishing system.
10/05/2004 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1504.6.4 Fire extinguishers - A portable fire extinguisher with a rating of 4A40B shall be within 30 feet of the spray booth.
10/05/2004 VIOL - HAZARDOUS MATERIALS,GEN TKNAPP Correction Required 2703.5 Hazard identification signs - Visible hazard identification signs shall be posted on the paint storage area.
10/05/2004 VIOL - FLAMMABLE LIQUIDS TKNAPP Correction Required 3404.3.4.4 Flammable liquids in excess of 10 gallons used for maintenance of equipment shall be stored in a liquid storage cabinet.