Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T04FR00438

Parcel: 11505171B


Addresses:

2200 N 7TH AV


Inspection Status: Correction Required

Inspection History: VIOL - FLAMMABLE FINISHES

Case Number - T04FR00438

Inspection Description - VIOL - FLAMMABLE FINISHES

Inspection Status - Correction Required

Date Description Inspector Results Comments
10/05/2004 VIOL - FLAMMABLE FINISHES Correction Required 1503.2.6 Smoking Prohibited - No smoking signs shall be posted near spray booth area and near paint storage area.
10/05/2004 VIOL - FLAMMABLE FINISHES Correction Required 1504.6.4 Fire extinguishers - A portable fire extinguisher with a rating of 4A40B shall be within 30 feet of the spray booth.
10/05/2004 VIOL - FLAMMABLE FINISHES Correction Required 1504.6 Fire Protection - Spray booths shall be protected by an approved automatic fire extinguishing system.
10/05/2004 VIOL - FLAMMABLE FINISHES Correction Required 1503.2.1.1 Spray spaces and vapor areas - Electrical wiring and equipment in spray spaces and vapor areas shall be of an explosion proof type.
10/05/2004 VIOL - FLAMMABLE FINISHES Correction Required 1504.1.2.5 Clear space - A clear space of 3 feet shall be maintained around spray booths.
10/05/2004 VIOL - FLAMMABLE FINISHES Correction Required 1503.2.7 Welding warning signs - Welding warning signs shall be posted near spray booth.