Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FLAMMABLE FINISHES
Case Number - T04FR00438
Inspection Description - VIOL - FLAMMABLE FINISHES
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2004 | VIOL - FLAMMABLE FINISHES | Correction Required | 1503.2.6 Smoking Prohibited - No smoking signs shall be posted near spray booth area and near paint storage area. | |
10/05/2004 | VIOL - FLAMMABLE FINISHES | Correction Required | 1504.6.4 Fire extinguishers - A portable fire extinguisher with a rating of 4A40B shall be within 30 feet of the spray booth. | |
10/05/2004 | VIOL - FLAMMABLE FINISHES | Correction Required | 1504.6 Fire Protection - Spray booths shall be protected by an approved automatic fire extinguishing system. | |
10/05/2004 | VIOL - FLAMMABLE FINISHES | Correction Required | 1503.2.1.1 Spray spaces and vapor areas - Electrical wiring and equipment in spray spaces and vapor areas shall be of an explosion proof type. | |
10/05/2004 | VIOL - FLAMMABLE FINISHES | Correction Required | 1504.1.2.5 Clear space - A clear space of 3 feet shall be maintained around spray booths. | |
10/05/2004 | VIOL - FLAMMABLE FINISHES | Correction Required | 1503.2.7 Welding warning signs - Welding warning signs shall be posted near spray booth. |