Case: T04FR00416
Case Details
Entered Date:
09/29/2004
Applicant:
GEE JANE TR
Description:
Inspection
Outstanding Inspections
Case Number: T04FR00416
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
09/29/2004 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.3- Outside storage. outside storage of combustibles shall not be located within 10 feet of a property line. The separation distance is allowed to be reduced to 3 feet for storage not exceeding 6 feet in height. Remove combustible liquids. |
09/29/2004 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- Working space and clearance. A minimum of 36 inches shall be provided in front of electrical service equipment. |
09/29/2004 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords. Ext. cords shall not be used as a substitute for permanent wiring. 1. ext. cord on N wall, E side 2. ext. cord on E wall |
09/29/2004 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1006.3- Illumination emergency power. In the event of a power failure, an emergency electrical system shall automatically illuminate exit access corridors, passageways and aisles in rooms and spaces which require 2 or more means of egress. 1. kitchen area 2. bar/restaurant area 3. assembly room |
09/29/2004 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1008.1.9- Panic and fire exit hardware. Each door in a means of egress from an occupancy of group A or E having an occupant load of 100 or more shall not be provided with a lock or latch unless it is panic hardware or fire exit hardware. 1. door on E wall of assembly room needs panic hardware. |
09/29/2004 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1026.3- Exit sign illumination. Exit signs shall be internally or externally illuminated. 1. exit sign on E wall, S side. 2. exit sign on W wall of assembly room. 3. exit sign on E wall, N side. |
09/29/2004 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1026.5- Illumination emergency power. In the event of a power failure, illumination shall be provided. 1. exit sign on E wall, S side. 2. exit sign on W wall of assembly room. 3. exit sign on E wall, N side. |
09/29/2004 | VIOL - COMPRESSED GASES | JLANGEJA | Violation | TFC 3003.3- Security. Compressed gas cylinders shall be secured against accidental dislodgement. 1. compressed gas cylinder behind bar needs to be secured. 2. compressed gas cylinders outside need to be secured or removed from premises. |