Case: T04FR00416

Parcel: 136061560


Addresses:

2440 S HARRISON RD


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T04FR00416

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
09/29/2004 VIOL - MEANS OF EGRESS Violation TFC 1006.3- Illumination emergency power. In the event of a power failure, an emergency electrical system shall automatically illuminate exit access corridors, passageways and aisles in rooms and spaces which require 2 or more means of egress.
1. kitchen area
2. bar/restaurant area
3. assembly room
09/29/2004 VIOL - MEANS OF EGRESS Violation TFC 1008.1.9- Panic and fire exit hardware. Each door in a means of egress from an occupancy of group A or E having an occupant load of 100 or more shall not be provided with a lock or latch unless it is panic hardware or fire exit hardware.
1. door on E wall of assembly room needs panic hardware.
09/29/2004 VIOL - MEANS OF EGRESS Violation TFC 1026.3- Exit sign illumination. Exit signs shall be internally or externally illuminated.
1. exit sign on E wall, S side.
2. exit sign on W wall of assembly room.
3. exit sign on E wall, N side.
09/29/2004 VIOL - MEANS OF EGRESS Violation TFC 1026.5- Illumination emergency power. In the event of a power failure, illumination shall be provided.
1. exit sign on E wall, S side.
2. exit sign on W wall of assembly room.
3. exit sign on E wall, N side.