Inspection Status: Violation
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T04FR00416
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/29/2004 | VIOL - MEANS OF EGRESS | Violation | TFC 1006.3- Illumination emergency power. In the event of a power failure, an emergency electrical system shall automatically illuminate exit access corridors, passageways and aisles in rooms and spaces which require 2 or more means of egress. 1. kitchen area 2. bar/restaurant area 3. assembly room |
|
09/29/2004 | VIOL - MEANS OF EGRESS | Violation | TFC 1008.1.9- Panic and fire exit hardware. Each door in a means of egress from an occupancy of group A or E having an occupant load of 100 or more shall not be provided with a lock or latch unless it is panic hardware or fire exit hardware. 1. door on E wall of assembly room needs panic hardware. |
|
09/29/2004 | VIOL - MEANS OF EGRESS | Violation | TFC 1026.3- Exit sign illumination. Exit signs shall be internally or externally illuminated. 1. exit sign on E wall, S side. 2. exit sign on W wall of assembly room. 3. exit sign on E wall, N side. |
|
09/29/2004 | VIOL - MEANS OF EGRESS | Violation | TFC 1026.5- Illumination emergency power. In the event of a power failure, illumination shall be provided. 1. exit sign on E wall, S side. 2. exit sign on W wall of assembly room. 3. exit sign on E wall, N side. |