Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

09/10/2004

Applicant:

ARIZONA BOARD OF REGENTS

Description:

inspection John- I finally have the answer! This is it! The University Services Building (i.e. Main Gate, 888 N. Euclid) does indeed belong to the University of Arizona. The land is owned by the Marshal Foundation, but the building is lease/owned by the UA. So we will be taking care of the inspection items that Effram forwarded on to Jose. The confusion came from our Space Management Department. When I asked the question, they thought I was referring to the new Marshal Foundation building on Park at 2nd Street. THAT building is completely owned by Marshal Foundation, even though the UA occupies the upper floors. You can have at that one. Thanks for all your efforts with USB (inspections, drills, etc.). We will be now listing the University Services Building (USB) on our inspection and alarm testing list. -Herb

Outstanding Inspections

Case Number: T04FR00364
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 11
End Date Description Inspector Results Comments
09/10/2004 INSP - FULL EGRIFFIN Violation 1). Fire alarm shall be tested and repaired, and test results shall be submitted to TFD. TFC 901.6
09/10/2004 INSP - FULL EGRIFFIN Violation 10). Area of refuge light is out of service and shall be repaired TFC 1026.3
09/10/2004 INSP - FULL EGRIFFIN Violation 11). Exit sign shall be added to Bursars office as discussed 1026.1
09/10/2004 INSP - FULL EGRIFFIN Violation 2). Fire sprinkler system shall be tested and repaired, and test results shall be submitted to TFD. TFC 901.6
09/10/2004 INSP - FULL EGRIFFIN Violation 3). Fire pump shall be tested and repaired, and test results shall be submitted to TFD. TFC 901.6
09/10/2004 INSP - FULL EGRIFFIN Violation 4). Fire drill shall be conducted. Date of drill to be determined by 10-12-04. TFC 404.2
09/10/2004 INSP - FULL EGRIFFIN Violation 5). Emergency generator shall be tested and log of testing shall be submitted to TFD 604.3.1 and 604.3.2
09/10/2004 INSP - FULL EGRIFFIN Violation 6). Storage is within 2 feet of ceilings in this sprinklered building and shall be lowered in the following areas: 501C, 502B, and 414G, 203D
09/10/2004 INSP - FULL EGRIFFIN Violation 7). The following doors equipped with automatic door closer were found to be left open in the following areas: 301,308,310,501,510,202, this is in violation of TFC 703.2.2, which states: 703.2.2 Hold-open devices and closers. Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position.
09/10/2004 INSP - FULL EGRIFFIN Violation 8). Smoking is currently being done in the non-sprinklered balconies with combustible material. These conditions make a smoking a hazard. This practice shall cease. TFC 310.2
09/10/2004 INSP - FULL EGRIFFIN Violation 9). Extension cord to microwave shall be removed room 404. TFC 605.5