Inspection History Details
Inspection Status: Violation
Inspection History: INSP - FULL
Case Number - T04FR00364
Inspection Description - INSP - FULL
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/10/2004 | INSP - FULL | Violation | 1). Fire alarm shall be tested and repaired, and test results shall be submitted to TFD. TFC 901.6 | |
09/10/2004 | INSP - FULL | Violation | 2). Fire sprinkler system shall be tested and repaired, and test results shall be submitted to TFD. TFC 901.6 | |
09/10/2004 | INSP - FULL | Violation | 3). Fire pump shall be tested and repaired, and test results shall be submitted to TFD. TFC 901.6 | |
09/10/2004 | INSP - FULL | Violation | 4). Fire drill shall be conducted. Date of drill to be determined by 10-12-04. TFC 404.2 | |
09/10/2004 | INSP - FULL | Violation | 5). Emergency generator shall be tested and log of testing shall be submitted to TFD 604.3.1 and 604.3.2 | |
09/10/2004 | INSP - FULL | Violation | 6). Storage is within 2 feet of ceilings in this sprinklered building and shall be lowered in the following areas: 501C, 502B, and 414G, 203D | |
09/10/2004 | INSP - FULL | Violation | 7). The following doors equipped with automatic door closer were found to be left open in the following areas: 301,308,310,501,510,202, this is in violation of TFC 703.2.2, which states: 703.2.2 Hold-open devices and closers. Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position. |
|
09/10/2004 | INSP - FULL | Violation | 8). Smoking is currently being done in the non-sprinklered balconies with combustible material. These conditions make a smoking a hazard. This practice shall cease. TFC 310.2 | |
09/10/2004 | INSP - FULL | Violation | 9). Extension cord to microwave shall be removed room 404. TFC 605.5 | |
09/10/2004 | INSP - FULL | Violation | 10). Area of refuge light is out of service and shall be repaired TFC 1026.3 | |
09/10/2004 | INSP - FULL | Violation | 11). Exit sign shall be added to Bursars office as discussed 1026.1 |