Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T04FR00364

Parcel: 11504600B


Addresses:

888 N EUCLID AV


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T04FR00364

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
09/10/2004 INSP - FULL Violation 1). Fire alarm shall be tested and repaired, and test results shall be submitted to TFD. TFC 901.6
09/10/2004 INSP - FULL Violation 2). Fire sprinkler system shall be tested and repaired, and test results shall be submitted to TFD. TFC 901.6
09/10/2004 INSP - FULL Violation 3). Fire pump shall be tested and repaired, and test results shall be submitted to TFD. TFC 901.6
09/10/2004 INSP - FULL Violation 4). Fire drill shall be conducted. Date of drill to be determined by 10-12-04. TFC 404.2
09/10/2004 INSP - FULL Violation 5). Emergency generator shall be tested and log of testing shall be submitted to TFD 604.3.1 and 604.3.2
09/10/2004 INSP - FULL Violation 6). Storage is within 2 feet of ceilings in this sprinklered building and shall be lowered in the following areas: 501C, 502B, and 414G, 203D
09/10/2004 INSP - FULL Violation 7). The following doors equipped with automatic door closer were found to be left open in the following areas: 301,308,310,501,510,202, this is in violation of TFC 703.2.2, which states:
703.2.2 Hold-open devices and closers. Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position.
09/10/2004 INSP - FULL Violation 8). Smoking is currently being done in the non-sprinklered balconies with combustible material. These conditions make a smoking a hazard. This practice shall cease. TFC 310.2
09/10/2004 INSP - FULL Violation 9). Extension cord to microwave shall be removed room 404. TFC 605.5
09/10/2004 INSP - FULL Violation 10). Area of refuge light is out of service and shall be repaired TFC 1026.3
09/10/2004 INSP - FULL Violation 11). Exit sign shall be added to Bursars office as discussed 1026.1