Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

08/11/2004

Applicant:

NORVILLE ALLAN J & ALFENA

Description:

Fire Inspection

Outstanding Inspections

Case Number: T04FR00298
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
08/11/2004 INSP - SELF INSPECTION PROGRAM TKNAPP Correction Required
08/11/2004 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 Unapproved conditions. Approved covers shall be provided for electrical boxes. The outlet box in the vault room on the east side of the building shall be repaired.
08/11/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1003.2.10.4 Exit sign illumination. Exit signs shall be illuminated at all times. Exit signs leading to the north and south stairwell downstairs above the eastside breakroom door, and at the south stairwell upstairs shall be repaired.
08/11/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1003.2.11 Means of egress illumination. The means of egress shall be illuminated at all times. The emergency lighting upstairs, on the south wall of the mortgage area, and on the west wall near the north stairwell, shall be repaired.
08/11/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1003.3.1.8 Locks and Latches. Egress doors shall be readily openable from the egress side without the use of a key or special knowlege or effort. The two doors leading to the mortgage area (upstairs) shall be openable from the egress side (mortgage area side) without the use of a key.
08/11/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1003.3.1.8.1 Bolt Locks. Manually operated flush bolts are not permitted. The flush bolt on the south central storage room door that leads to the south stairwell shall be removed.