Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T04FR00298
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/11/2004 | VIOL - MEANS OF EGRESS | Correction Required | 1003.2.10.4 Exit sign illumination. Exit signs shall be illuminated at all times. Exit signs leading to the north and south stairwell downstairs above the eastside breakroom door, and at the south stairwell upstairs shall be repaired. | |
08/11/2004 | VIOL - MEANS OF EGRESS | Correction Required | 1003.2.11 Means of egress illumination. The means of egress shall be illuminated at all times. The emergency lighting upstairs, on the south wall of the mortgage area, and on the west wall near the north stairwell, shall be repaired. | |
08/11/2004 | VIOL - MEANS OF EGRESS | Correction Required | 1003.3.1.8.1 Bolt Locks. Manually operated flush bolts are not permitted. The flush bolt on the south central storage room door that leads to the south stairwell shall be removed. | |
08/11/2004 | VIOL - MEANS OF EGRESS | Correction Required | 1003.3.1.8 Locks and Latches. Egress doors shall be readily openable from the egress side without the use of a key or special knowlege or effort. The two doors leading to the mortgage area (upstairs) shall be openable from the egress side (mortgage area side) without the use of a key. |