Case: T04FR00288
Case Details
Entered Date:
08/06/2004
Applicant:
WILSON JEAN F & CHARLES TRUSTEES
Description:
Annual Inspection
Outstanding Inspections
Case Number: T04FR00288
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/05/2004 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 304.1.1- combustible waste shall not be permitted (outside around electrical vault) |
| 08/05/2004 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.2- combustible materials shall not be stored in exit aisles (drive-thru teller room) |
| 08/05/2004 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.3- equipment rooms. combustible materials shall not be stored in electrical room. |
| 08/05/2004 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.1- electrical hazards shall be abated 1. junction box on west wall (outside) 2. floor recepticle needs cover (military room) 3. junction box in vault room needs cover 4. junction box in small vault room |
| 08/05/2004 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- working space and clearance of not less than 30" in width, 36" in depth and 78" in height shall be provided |
| 08/05/2004 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Violation | TFC 703.1- fire resistive construction shall be maintained (ceiling tiles in ATM room) |
| 08/05/2004 | VIOL - COMPRESSED GASES | JLANGEJA | Violation | TFC 3003.3.3- compressed gas cylinders shall be secured in an approved manner |