Case: T04FR00288

Parcel: 12105012D


Addresses:

5502 E GRANT RD


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T04FR00288

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
08/05/2004 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.1- electrical hazards shall be abated
1. junction box on west wall (outside)
2. floor recepticle needs cover (military room)
3. junction box in vault room needs cover
4. junction box in small vault room
08/05/2004 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- working space and clearance of not less than 30" in width, 36" in depth and 78" in height shall be provided