Case: T03VL00688
Case Details
Entered Date:
07/22/2003
Applicant:
MTA PARTNERS LLC
Description:
COMPLAINT:EMERGENCY CALLOUT - ELECTRICAL SHORTOUT
Outstanding Inspections
Case Number: T03VL00688
Case Status: COMPLIAN
Case Description: RES: FIRE
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2003 | INITIAL CODE VIOLATION | RMAJUTA | Violation | DAMAGE REPORT: CAUSE: SERVICE ENTRANCE CONDUCTORS SHORTED OUT AND FUSED JUST PAST WEATHER HEAD IN RISER; LOCATION: EXTERIOR EAST WALL SERVICE LOCATION; ELECTRICAL: TWO-WIRE SERVICE 120V 30 AMP, APPEARS WIRES FUSED TOGETHER IN RISER - MAY HAVE BEEN TENSION ON DROP. 30 AMP SERVICE HAS NO NEUTRAL CONNECTION OR LANDING IN 30 AMP SWITCH, DOUBLE LUGGING ON SECONDARY #6 WIRES AND #10 WIRE WRAPPED AROUND SIREN. 30 AMP FUSES FEEDING PORCELAIN LIGHT AND RECEPTACLE. ALL OF THE PROBELMS ABOVE AND AGE CONSTITUTE REQUIREMENT FOR A SERVICE UPGRADE THIS SERVICE WILL NOT BE RENERGIZED. SUMMARY: A PERMIT FOR A SERVICE UPGRADE REQUIRED AND AN INSPECTION IN ORDER TO RE-ENGERIZE. OBTAIN PERMIT AT 201 N STONE AV. NOTICE OF DAMAGE GIVEN TO ELENA RUSSELL OWNERS EMPLOYEE. |
Completed Inspections
Case Status: COMPLIAN
Case Number: T03VL00688
Case Description: RES: FIRE
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/23/2003 | FOLLOW UP CODE VIOLATION | RMAJUTA | Approved | PERMIT T03EL01371 ISSUED 07/15/03, FINALED 07/21/03 |