Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T03VL00559
Case Details
Entered Date:
06/04/2003
Applicant:
4D PROPERTIES
Description:
COMPLAINT:EMERGENCY CALLOUT - FIRE - MEGA WASH
Outstanding Inspections
Case Number: T03VL00559
Case Status: COMPLIAN
Case Description: COM: FIRE
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/03/2003 | INITIAL CODE VIOLATION | DSANTACR | Violation | EMERGENCY CALLOUT: FIRE IN LAUNDRY ROOM ELECTRICAL FIRE IN DRYERS AT LAUNDRY FACILITIES, CAUSE UNKNOWN. FIRE DEPT OPENED DISCONNECT SWITCHES TO DRYERS TO SHUT OFF POWER. OWNER ARRIVED, ELECTRICAL INSPECTOR GAVE OWNER NOV FOR UNSAFE WIRING. |
06/03/2003 | INITIAL CODE VIOLATION | DSANTACR | Violation | NOV ISSUED/SIGNED BY TODD PAUL FOR ELECTRICAL WIRING BEHIND DRYERS EXPOSED, AND NOT INSTALLED PROPERTY, FIRE HAZARD. THE DISCONNECT SWITCHES TO THE DRYERS ARE TO BE LEFT OFF. OWNER TO ARRANGE FOR L-11 ELECTRICAL LICENSED CONTRACTOR TO MAKE REPAIRS NECESSARY FOR A SAFE AND OPERATIONAL SYSTEM. OBTAIN 2 HOUR PERMIT FOR ELECTRICAL REPAIR. F/U 06/17/03 |
Completed Inspections
Case Status: COMPLIAN
Case Number: T03VL00559
Case Description: COM: FIRE
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/18/2003 | FOLLOW UP CODE VIOLATION | DSANTACR | Approved | PERMIT T03EL01210 ISSUED 06/20/03 |