Inspection History Details
Inspection Status: Violation
Inspection History: INITIAL CODE VIOLATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2003 | INITIAL CODE VIOLATION | Violation | EMERGENCY CALLOUT: FIRE IN LAUNDRY ROOM ELECTRICAL FIRE IN DRYERS AT LAUNDRY FACILITIES, CAUSE UNKNOWN. FIRE DEPT OPENED DISCONNECT SWITCHES TO DRYERS TO SHUT OFF POWER. OWNER ARRIVED, ELECTRICAL INSPECTOR GAVE OWNER NOV FOR UNSAFE WIRING. |
|
| 06/03/2003 | INITIAL CODE VIOLATION | Violation | NOV ISSUED/SIGNED BY TODD PAUL FOR ELECTRICAL WIRING BEHIND DRYERS EXPOSED, AND NOT INSTALLED PROPERTY, FIRE HAZARD. THE DISCONNECT SWITCHES TO THE DRYERS ARE TO BE LEFT OFF. OWNER TO ARRANGE FOR L-11 ELECTRICAL LICENSED CONTRACTOR TO MAKE REPAIRS NECESSARY FOR A SAFE AND OPERATIONAL SYSTEM. OBTAIN 2 HOUR PERMIT FOR ELECTRICAL REPAIR. F/U 06/17/03 |