Case: T03VL00364
Case Details
Entered Date:
03/25/2003
Applicant:
AHMAD MAQSOOD & SABINA JT/RS
Description:
EMERGENCY: FIRE IN CARPORT
Outstanding Inspections
Case Number: T03VL00364
Case Status: COMPLIAN
Case Description: COM: FIRE
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2003 | INITIAL CODE VIOLATION | RMAJUTA | Correction Required | REVIEWED FIRE DAMAGE VERIFIED POWER ANDGAS OFF. ISSUED NOTICE TO OCCUPANT ADVISED HOW TO GET RECONNECTED. CAUSE OF DAMAGE: FIRE IN CARPORT & STORAGE ROOM AREA. BUILDING: FRAMING AROUND STORAGE RM & CEILING BADLY FIRE DAMAGED TO BE REPLACED CRPORT AND RAFTERS ABOVE CARPORT FIRE DAMAGED. SOME SHEET ROCK DAMAGE INSIDE. ELECTRICAL: CIRCUIT GOING OUT TO STORAGE ROOM BURNT WILL NEED TO GET ELECTRICIAN TO DISCONNECT PORTION DAMAGED IN ORDER TO GET RECONNECT. PLUMBING NONE HOWEVER SW GAS HAD GAS METER SHUT DUE TO FIRE WILL NEED A PERMIT AND PRESSURE GAS TEST ON LINES TO GET TURNED ON. MECHANICAL: NONE SUMMARY REMARK: YOU CAN GET RECONNECT ONCE ELECTRICIAN ISOLATED DAMAGED RECONNECT BY CALLING ELECTRICAL INSPECTOR. FOLLOW UP 4/21/03 |
Completed Inspections
Case Status: COMPLIAN
Case Number: T03VL00364
Case Description: COM: FIRE
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/27/2003 | FOLLOW UP CODE VIOLATION | MTESTER | Approved | OWNER IS REQUESTING AN EXTENSION TO 17 DEC. 03 REQUEST GRANTED. |
Completed Activity Special Conditions
Case Description - COM: FIRE
Case Number - T03VL00364
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 1
| Date | Name |
| 09/10/2003 | NOTICE OF VIOLATION ISSUED |