Case Details

Status:

CLOSED

Type:

COM: FIRE
Address:

Entered Date:

10/09/2002

Applicant:

GEE HENRY & GEE ROSE TR

Description:

FIRE: ELECTRIC FIRE

Outstanding Inspections

Case Number: T02VL02055
Case Status: CLOSED
Case Description: COM: FIRE
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
10/03/2002 INITIAL CODE VIOLATION RMAJUTA Correction Required 1.) THE 600AMP ELECTRICAL SERVICE IS IN A INADEQUATELY MAINTAINED, DILPITADEA OBSOLESCENT CONDITION. THE COPPER BUS IN THE 600A DISCONNECT IS DISCOLORED BY HEAT AND COPRODED, THE INSULATION IS OLD AND BRITTLE ON THE CONDUCTORS THIS CALL FOR REPLACEMENT ON THIS DISCONNECT. 2.) THE GAS LINE IN FRONT OF THE SERVICE NEEDS TO BE REMOVED DUE TO CLEARANCE REQUIREMENTS. 3.) THE REST OF THE SERVICE ALSO IN NEED OF REPLACEMENT DUE TO SERIOUS DOUBLE AND TRIPLE LUGGING, INADEQUATE OVER CURRENT PROTECTION, IMPROPER WIRING METHODS NON APINTIGHT EQUIPMENT, OLD AGE, INADEQUATE MAINTENANCE AND DETERIORATION OF EQUIPMENT. 4.) THE FIRE DAMAGED FEEDERS NEE REPLACEMENT,EXISTING PANELS A-B-C HAVE BEEN IMPROPERLY ADDED TO OVER THE YEARS AND AGE, INADEQUATE MAINTENANCE

Completed Inspections

Case Status: CLOSED
Case Number: T02VL02055
Case Description: COM: FIRE
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/25/2002 FOLLOW UP CODE VIOLATION RSUBA Approved PERMIT TAKEN OUT AND WORK STARTED ON CORRECTION.

Completed Activity Special Conditions

Case Description - COM: FIRE
Case Number - T02VL02055
Case Status: CLOSED
Total Completed Case Activity Conditions: 1
Date Name
10/30/2002 PERMIT ISSUED - T02CM04873 AND T02CM04091