Case: T02VL02055

Parcel: 131010250


Addresses:

4828 E 22ND ST


Inspection Status: Correction Required

Inspection History: INITIAL CODE VIOLATION

Case Number - T02VL02055

Inspection Description - INITIAL CODE VIOLATION

Inspection Status - Correction Required

Date Description Inspector Results Comments
10/03/2002 INITIAL CODE VIOLATION Correction Required 1.) THE 600AMP ELECTRICAL SERVICE IS IN A INADEQUATELY MAINTAINED, DILPITADEA OBSOLESCENT CONDITION. THE COPPER BUS IN THE 600A DISCONNECT IS DISCOLORED BY HEAT AND COPRODED, THE INSULATION IS OLD AND BRITTLE ON THE CONDUCTORS THIS CALL FOR REPLACEMENT ON THIS DISCONNECT. 2.) THE GAS LINE IN FRONT OF THE SERVICE NEEDS TO BE REMOVED DUE TO CLEARANCE REQUIREMENTS. 3.) THE REST OF THE SERVICE ALSO IN NEED OF REPLACEMENT DUE TO SERIOUS DOUBLE AND TRIPLE LUGGING, INADEQUATE OVER CURRENT PROTECTION, IMPROPER WIRING METHODS NON APINTIGHT EQUIPMENT, OLD AGE, INADEQUATE MAINTENANCE AND DETERIORATION OF EQUIPMENT. 4.) THE FIRE DAMAGED FEEDERS NEE REPLACEMENT,EXISTING PANELS A-B-C HAVE BEEN IMPROPERLY ADDED TO OVER THE YEARS AND AGE, INADEQUATE MAINTENANCE