Case Details

Status:

Active

Type:

(Via 311): No adequate exterior lights on four floors of the buildings staircases since August 1. Handicap lives in building and using flashlights have raised huge concerns.
Address:

Entered Date:

09/15/2025

Applicant:

N/A

Description:

Completed Inspections

Case Status: Active
Case Number: CE-VIO0925-04014
Case Description: (Via 311): No adequate exterior lights on four floors of the buildings staircases since August 1. Handicap lives in building and using flashlights have raised huge concerns.
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/10/2025 COT - ENFC - Code Enforcement - Initial In Violation All exterior lights to each apartment entrance have been removed and covered with a plate. L.E.D. rope lights have been installed on new electrical circuits, attached to underneath of the walkways in lieu of permanent lighting. Manufacture’s installation labels indicate that the rope lights must be energized by ground fault interruption circuits. The receptacles energizing these cords do not appear to be protected as required. Some areas of these rope lights have signs of damage and is being suspended by bare metal wire. The nonmetallic electrical cable energizing these rope lights have a date stamp of 5/19/2024, no permit can be found on record. Large portion of the individual electrical service panels are not clearly labeled for identification. 4th floor east side has two (6) pack meter system and gutter box that is not attached to the building and is only being supported by conduit. 3rd floor east side has two (6) pack meter system and gutter box that is not attached to the building and is only being supported by conduit. Unit T8 is boarded and appears to be occupied. Unit T14 is vacant and has damaged window glazing materials. Its currently boarded. Unit D14 is vacant and has damaged/ missing window glazing material. Unit C22 is vacant and has damaged window glazing material. Unit C31 is currently vacant and boarded. Potential unit A-9 is missing its identifying unit number and is boarded.

Scheduled Inspections

SCase Number - CE-VIO0925-04014
Case Status: Active
Case Description:
Scheduled Date Description Inspector Status
12/17/2025 COT - ENFC - Code Enforcement - Follow Up Scheduled