Type:

CWOP: Installation of Griddle and vent hood without permits. Hood and fire suppression systems not installed as required by 2024 IMC § 507.2 (Type I hood required) and 2024 IBC § 904.2.2 and § 904.14 (automatic fire-extinguishing/suppression system required).
Address:

Entered Date:

08/27/2026

Applicant:

N/A

Description:

Completed Inspections

Case Status: Active
Case Number: CE-VIO0826-03593
Case Description: CWOP: Installation of Griddle and vent hood without permits. Hood and fire suppression systems not installed as required by 2024 IMC § 507.2 (Type I hood required) and 2024 IBC § 904.2.2 and § 904.14 (automatic fire-extinguishing/suppression system required).
Total Completed Inspections - 1
End Date Description Inspector Results Comments
10/02/2026 COT - ENFC - Code Enforcement - Initial In Violation On site, I observed a stove ad cooking hood installed inside of the kitchen. There is not an approved permit for the hood system. I issued an NOV for the permitting of the hood. Owner submitted what he says he thought was the application for the permit,. However, he was not correct about that, so i informed him that he must resubmit for the permit. He acknowledged and agreed to finish the permit process.